LAMP BALLAST TYPE TOTAL LIGHT LOSS FACTOR (LLF)
     
13W PLC COMPACT FLUORESCENT ELECTRONIC 0.77
18W PLC COMPACT FLUORESCENT ELECTRONIC 0.77
26W PLC COMPACT FLUORESCENT ELECTRONIC 0.77
     
18W PLT COMPACT FLUORESCENT ELECTRONIC 0.77
26W PLT COMPACT FLUORESCENT ELECTRONIC 0.77
32W PLT COMPACT FLUORESCENT ELECTRONIC 0.75
42W PLT COMPACT FLUORESCENT ELECTRONIC 0.75
     
40W PLL COMPACT FLUORESCENT ELECTRONIC 0.81
50W PLL COMPACT FLUORESCENT ELECTRONIC 0.89
55W PLL COMPACT FLUORESCENT ELECTRONIC 0.76
80W PLL COMPACT FLUORESCENT ELECTRONIC 0.80
     
14W T5 FLUORESCENT ELECTRONIC 0.90
24W T5HO FLUORESCENT ELECTRONIC 0.86
28W T5 FLUORESCENT ELECTRONIC (EB95) 0.81
28W T5 FLUORESCENT ELECTRONIC (EB115) 0.98
28W T5 FLUORESCENT ELECTRONIC (EB) 0.86
54W T5HO FLUORESCENT ELECTRONIC 0.86
80W T5HO FLUORESCENT ELECTRONIC 0.86
     
17W T8 LINEAR FLUORESCENT ELECTRONIC 0.74
17W T8 LINEAR FLUORESCENT ELECTRONIC-HIGH BALLAST FACTOR 1.08
25W T8 LINEAR FLUORESCENT ELECTRONIC 0.73
32W T8 LINEAR FLUORESCENT ELECTRONIC-STANDARD 0.75
32W T8 LINEAR FLUORESCENT ELECTRONIC-LOW BALLAST FACTOR 0.66
32W T8 LINEAR FLUORESCENT ELECTRONIC-HIGH BALLAST FACTOR 1.02
32W T8 U-BENT FLUORESCENT ELECTRONIC 0.72
59W T8 8' SLIMLINE FLUORESCENT ELECTRONIC 0.70
86W T8 8' HO FLUORESCENT ELECTRONIC 0.71
     
40W T12 LINEAR FLUORESCENT MAGNETIC 0.77
75W T12 SLIMLINE FLUORESCENT MAGNETIC 0.88
110W T12 8' HO FLUORESCENT MAGNETIC 0.77
     
175W STANDARD METAL HALIDE CWA 0.59
250W STANDARD METAL HALIDE CWA 0.59
400W STANDARD METAL HALIDE CWA 0.59
1000W STANDARD METAL HALIDE CWA 0.58
     
175W PULSE START METAL HALIDE CWA 0.72
200W PULSE START METAL HALIDE CWA 0.72
250W PULSE START METAL HALIDE CWA 0.72
320W PULSE START METAL HALIDE CWA 0.72
350W PULSE START METAL HALIDE CWA 0.72
400W PULSE START METAL HALIDE CWA 0.72
450W PULSE START METAL HALIDE CWA 0.72
875W PULSE START METAL HALIDE CWA 0.72
1000W PULSE START METAL HALIDE CWA 0.72
     
100W HPS ALL 0.81
150W HPS ALL 0.81
200W HPS ALL 0.81
310W HPS ALL 0.81
400W HPS ALL 0.81
1000W HPS ALL 0.81
     